Airlock interlock, buffer interlock, two-door interlock, three-door interlock

Two-door interlock airlock buffer room Electronic interlock This product is widely used in purification industry, such as purification plant buffer room, air lock room, dressing room, etc., by the full metal shell fuselage, with LED indicator light, more intuitive use, more convenient operation.
Strictly control the flow of people or logistics in the air lock room/buffer room, improve clean efficiency, used to control the door of the air lock room/buffer room can only open one door, play an interconnection role, when a door is opened, other locks are locked at the same time, after 10 seconds or so, the buzzer will issue an alarm to prompt the user to close the door, when a door is opened for more than a certain time, The other door will automatically open the lock, as a misoperation, after closing to restore its original function, in the case of power failure, the electronically controlled lock of each door will automatically open, greatly improving work efficiency.
1. Buzzer reminder 2. Error correction 3.2 Level protection 4. Aluminum alloy housing 5. Stainless steel lock head 6. Multi-door interlock control

Features:

Automatic interlocking, 90-second reset
The interlocking device is specially designed for the air isolation of the purification workshop, and is generally used in the air lock room or buffer room of the purification workshop, so that the door of the room can not be opened at the same time, so as to ensure the effective isolation of the purification area and the non-purification area. This device is divided into ST-2, ST-3 series, the main components are: main controller 1 set, 2 electric control lock (ST-3 electric control lock 3). The system uses the working mode of power on the lock, so that it will not open the door in the power failure or emergency, to avoid unnecessary losses, the system itself has low power consumption, long service life, is the ideal product for purification engineering.

1. Instructions for use:
1. Initialize self-test
Power on, turn on (power), hear the buzzer, the system automatically detects whether the two doors are closed. If one door is not closed, the buzzer starts to alarm (the buzzer continuously buzzes) to remind the user to close both doors. If the buzzer stops ringing, the system starts to work normally.
2. Work normally
If door A is opened, door B is locked. (If door A is not closed for A long time, the buzzer alarms) Employees enter the airlock, close door A (door B is open), employees open door B (door A is locked), employees enter the clean area (if door B is not closed for a long time, the buzzer alarms), and then close door B, door A is opened, and the process from the unclean area to the clean area is over.
If door B is opened, door A is locked. (If door B is not closed for A long time, the buzzer alarms) Employees enter the airlock room, close door B (door A is open), employees open door A (door B is locked), employees enter the unclean area (if door A is not closed for a long time, the buzzer alarms), and then close door A, door B is opened, and the process from clean area to unclean area is over.

The system adopts imported computer chip, which has high stability, high accuracy, small size and complete functions. The system has a power consumption of less than 12w, a low temperature rise and a longer lock life, making it ideal for the purification industry.



First, the working principle

1, turn on the power switch after the power supply, the two doors are closed, the system starts to work normally. When the outer door is opened, the other inner door is automatically locked, the employee enters the air lock room, must close the outer door, in order to open the inner door, and then close the inner door.

2, when a door is open for 10 seconds and still not closed, the buzzer will sound (dud-dud-dudu) to remind the user to close the door.

3, when one door is opened 180 seconds later, the other door is automatically unlocked.

4, in the case of power failure, the electric lock will be automatically unlocked, and both doors can be opened.

5, If there is an emergency, you can press the reset button to force the unlock.



Second, installation method

1, electric lock installation: open a diameter 32mm round hole (electric lock installation hole) and a diameter 18mm round hole (door magnetic switch installation hole) in the door frame, insert the electric lock connection line in the direction of the slot and then insert the lock body, and then drill two 4.2mm round holes according to the fixed holes on the lock plate, and fix them with 4*10mm core-pulling aluminum rivets. Connect the door status sensor cable to the door status sensor.

2, lock plate installation: after the lock body is installed, according to the position of the lock plate to determine the position of the lock plate, and then according to the shape of the lock plate on the side of the door to open a 45mm*35mm rectangular hole, put the lock plate and then use the same method to fix the lock plate.

3, door magnetic switch installation: door magnetic switch B installed on the door, open A diameter of 18mm round hole, the opening hole should be aligned with the door magnetic switch A. (Please refer to the installation diagram for electric lock, lock plate and door magnetic switch)

4. Indicator light installation: The indicator light is installed next to or in a more eye-catching position, and the opening size is 130mm*50mm. The indicator can be inserted into either of two ports.

5, the control box installation: the control box is fixed at the top of the airlock, the two connecting lines are connected to the electric lock, and the 220V power supply can be used normally.



Iii. Precautions:

1. The chain must be used in conjunction with door closers or ordinary door locks. It is best to install three closed leaves to prevent the door from sagging, so as not to affect the uniformity of the lock piece. When the door gap is large, the rubber board is used to adjust the gap between the lock and the stainless steel lock piece. Lock plate and electric lock panel must be aligned.

2. Please note the direction when inserting the cable into the lock body and control box.

3, the two installation positions of the electric lock can be selected according to the actual situation.



4. Troubleshooting

1, there is no reaction after power: a, check whether the power socket has 220V; b, check whether the fuse is disconnected;

2, can not work properly: a, check whether the lock piece is aligned; b. Check whether the door magnetic switch is aligned; c, check whether the connection cable is inserted;

Special requirements: You can contact us, such as replacing the electric lock (electromagnetic lock, electric plug lock, electric lock port, etc.) whether to add the emergency switch controller center